Generator Set Specifications
- Maximum Rating
-
2750 kVA
- Minimum Rating
-
2500 kVA
- Emissions/Fuel Strategy
-
Low Fuel, Low Emissions
- Voltage
-
380 to 11000 volts
- Frequency
-
50 Hz
- Speed
-
1500 rpm
- Duty Cycle
-
Standby, Mission Critical, Prime
Engine Specifications
- Engine Model
-
3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
- Bore
-
6.69in
- Stroke
-
8.46in
- Displacement
-
4764.73in
- Compression Ratio
-
14.7:1
- Aspiration
-
TA
- Fuel System
-
Electronic unit injection
- Governor Type
-
Ademā¢3
Generator Set Dimensions
- Length - Maximum
-
297.4in
- Width - Maximum
-
108.9in
- Height - Maximum
-
118.3in
- Dry Weight - Genset (maximum)
-
39090lb
Standard Equipment:
-
- Air Inlet
-
-
- Cooling
-
-
- Exhaust
-
-
- Fuel
-
- Fuel priming pump
- Secondary fuel filter
- Primary fuel filter with integral water separator
-
- Generator
-
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
-
- Power Termination
-
-
- Control Panel
-
-
- General
-
- Paint - Caterpillar Yellow except rails and radiators gloss black
Optional Equipment:
-
- Exhaust
-
-
- Generator
-
- Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
- Anti-condensation heater
- Oversize and premium generators
-
- Power Termination
-
- Circuit breakers, IEC compliant
- Circuit breakers, UL listed
-
- Control Panels
-
- EMCP 4.3, EMCP 4.4
- Digital I/O module
- Load share module
- Generator temperature monitoring & protection
- Remote monitoring software
-
- Mounting
-
- Spring-type vibration isolator
- Rubber anti-vibration mounts
- IBC isolators
-
- Starting/charging
-
- Jacket water heater
- Charging alternator
- Oversize batteries
- Battery chargers
- Heavy-duty starting system
- Air starting motor with control and silencer
-
- General
-
- UL 2200 package
- EU Certificate of Conformance (CE)
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- EEC Declaration of Conformity
- Integral & sub-base UL listed dual wall fuel tanks
- The following options are based on regional and product configuration:
- Automatic transfer switches (ATS)
- Enclosures: sound attenuated, weather protective
- CSA Certification
- Integral & sub-base fuel tanks