Electric Power

Generator Set Specifications

Minimum Rating
1450 ekW
Maximum Rating
1750 ekW
Emissions/Fuel Strategy
Low Fuel, Low Emissions
Voltage
380 to 13800 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Engine Specifications

Engine Model
3516 TA, V-16, 4-Stroke Water-Cooled Diesel
Bore
6.69in
Stroke
7.48in
Displacement
4210.64in³
Compression Ratio
13.0:1
Aspiration
TA
Fuel System
Mechanical unit injection
Governor Type
Woodward

Generator Set Dimensions

Length - Maximum
247in
Width - Maximum
90in
Height - Maximum
94.9in
Dry Weight - Genset (maximum)
28840lb

Standard Equipment:

  • Air Inlet System
    • Air Cleaner; single element canister type
  • Control Panels
    • Accessory module data link
    • Low coolant level
    • Environmental sealed front face
    • EMCP 4.2B
    • 6 Customer programmable digital inputs
    • Communications:
    • Load histogram feature
    • Overspeed
    • Alarm acknowledge
    • kW-hr (total)
    • 24-volt DC operation
    • Over / Under voltage (27/59)
    • 1 programmable relay outputs (Form C)
    • kVAr-hr (total)
    • Emergency stop pushbutton
    • PLC functionality
    • Speed adjust
    • Lamp test
    • Auto / start / stop control
    • Over / Under Frequency (81 o/u)
    • Generator phase sequence
    • Revers Power (kW) (32)
    • Oil pressure (psi, kPa or bar
    • Coolant temperature
    • RPM
    • Overcurrent (50/51)
    • IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min / max exciter. Limiter and exciter diode monitor
    • Controls:
    • Number of I/O varies on options selected:
    • Power Factor (per phase & average)
    • 0 True RMS AC metering, 3-phase, +/-2% accuracy
    • kVA (per phase, average & percent
    • Serial annunciator module data link
    • Customizable screens
    • Generator mounted - rear facing
    • kW (per phase, average & percent)
    • Text alarm / event descriptions
    • DC volts
    • Low oil pressure
    • Controls: Speed adjust - Auto / start / stop control - Engine cool-down timer - Engine cycle crank - Alarm acknowledge - Lamp test - Load histogram feature - PLC functionality - Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
    • Reverse Reactive Power (kVAr) (32RV
    • Frequency (Hz
    • Low coolant temperature
    • 3 Analog inputs
    • Cat Connect
    • kVAr (per phase, average & percent)
    • Warning/shutdown with common LED indication of shutdowns for:
    • Engine cycle crank
    • Failure to start (overcrank)
    • Programmable protective relaying functions:
    • Emergency stop
    • Customer data link (Modbus RTU
    • Engine cool-down timer
    • Volts (L-L & L-N)
    • Amps (per phase & average)
    • Operating hours
    • High coolant temperature
    • Digital indication for:
    • 1 programmable digital outputs
    • 4 programmable relay outputs (Form A)
  • Cooling System
    • Certified standard PGS provided
    • ATAAC - 3516E Package Radiators shipped installed
  • Exhaust System
    • Flanged faced outlet(s)
    • Dry exhaust manifold
  • Fuel System
    • Secondary fuel filters
    • Fuel cooler; not included with packages without radiator
    • Flexible fuel lines - shipped loose
    • Fuel priming pump
  • General
    • Right hand servicing
    • Flywheel and flywheel housing - SAE No. 00
    • SAE Standard rotation
  • Generator And Attachments
    • NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime/150C standby)
    • NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime/150C standby)
    • Winding temperature detectors
    • Winding temperature detectors
    • Permanent magnet
    • Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
    • Six lead
    • Permanent magnet
    • Internal Excitation
    • 3 Phase brushless, salient pole
    • Winding temperature detectors
    • Medium Voltage:
    • Random wound
    • Anti Condensation Space Heater
    • Low Voltage:
    • High Voltage:
    • Busbar connections, top center mounted, top cable entry
    • Form wound
    • Bus bar connections, right side extension box, bottom cable entry
    • Form wound
    • NEMA standard hole pattern
    • NEMA standard hole pattern
  • Governing System
    • ADEM A3
  • Literature
    • English
  • Lubrication System
    • Fumes disposal
    • Lubricating oil
    • Gear type lube oil pump
    • Oil filter, filler and dipstick
    • Oil drain lines and valve
    • Integral lube oil cool
  • Mounting System
    • Rails - engine/generator/radiator mounting
    • Anti-vibration mounts (shipped loose)
    • Rubber anti-vibration mounts (shipped loose)
  • Starting System
    • Battery and battery rack w/cables
    • 45 Amp charging alternator
    • Battery disconnect switch
    • 24 Volt electric starting motor

Optional Equipment:

  • Control System
    • Controller: EMCP 4.2B
    • Local annunciator module: [ ] NFPA 110 [ ] Custom
  • Air Inlet System
    • Dual element air cleaner
    • Single element filter
  • Cooling System
    • Standard ambient radiators
    • Coolant
    • Optional installed ATAAC radiators
    • Optional installed radiators
    • Water level switch gauges
    • Standard ambient ATAAC radiators
  • Engine Options
    • Starting Motors: [ ] Standard [ ] Heavy Duty
    • Batteries: [ ] Standard (1400 CCA) [ ] Heavy Duty (2800 CCA)
    • Starting Aids: [ ] 220V 50 Hz Jacket Water Heater
    • Battery Charger: [ ] 10A [ ] 20A [ ] 35A
    • Air Cleaner: [ ] Single element air cleaners [ ] Dual element air cleaners [ ] Heavy duty air cleaners
    • Muffler: [ ] Industrial Grade
  • Crankcase System
    • No explosion relief valves
    • Ventilation system
    • Explosion relief valves
  • Alternators
    • Temperature Rise (over 40°C ambient): [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C
  • Exhaust System
    • Y-Adapters
    • Tier 4 clean emissions module
    • Tier 4 dosing cabinet
    • Elbows
    • Tier 4 clean emission MOD Kits
    • Exhaust offset
    • Flanges
    • Flange and exhaust expanders
    • Flexible fittings
    • Mufflers
    • Clean emission parts
  • Fuel System
    • Fuel Priming Pumps (Tier 4) - Manual or Electric
    • Primary Fuel Filter
  • General
    • US aid emblem
    • Special paint (Colors other than Caterpillar yellow or high performance paints)
    • The following options are based on regional and product configuration:
    • UL 2200 package
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • Generators And Attachments
    • High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
    • Generator conversion
    • Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
    • Thermostate for space heater
    • Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
    • Alternator air cleaner
    • Differential current transformers (DCT)
    • High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
    • Differntial current transformers (DCT) 8.7 kV and 15 kV classes
    • Space heater kits
  • Power Termination
    • Circuit breaker operation: [ ] Electrical
    • Circuit Breaker rating: [ ] 2000A [ ] 2500A [ ] 3200A [ ] 4000A
    • Circuit breaker trip unit: [ ] LSI [ ] LSIG [ ] LSIG-P
    • Power Termination: [ ] Bus Bar [ ] Circuit Breaker
  • Extended Service Contract (esc)
    • Extended Service Contract (ESC): [ ] 2 Year [ ] 3 Year [ ] 5 Year
  • Instrumentation
    • Pyrometer and Thermocouples
  • Lubrication System
    • Lube oil in standard sump
    • Prelube pumps
    • Oil level regulator
  • Mounting System
    • Puck style low efficiency isolators
    • Spring type vibration isolators
    • IBC vibration isolators
  • Power Connections
    • Ground cables between generator and terminal box
    • Neutral ground connections
    • 2700 Frame, four lead, four terminal
    • Rear power connections
    • Right side power connections
    • Left side power connections
    • Low voltage circuit breakers
    • Center post busbar
  • Special Tests / Reports
    • generator test report
    • OSHPD certification
    • Canadian Standards Association certification
    • PGS test report @ 1.0 power factor
    • IBC certification
    • Fuel consumption test
    • Generator set fuel consumption test
    • PGS test report @ 0.8 power factor
    • Standard engine test charge
    • Torsional vibration analysis reports
  • Starting And Charging
    • Electric starting motors
    • Air pressure regulator
    • Starter cover
    • Air starting motors
    • 24 Volt battery set - Dry
    • 10, 20, 35 and 50 amp battery chargers
    • Jacket water heaters
    • Engine barring device
  • Extended Service Coverage
    • Platinum, Gold and Silver coverage