Frequency |
60 Hz |
Fuel Type |
Natural Gas |
Maximum Continuous Rating |
1300 ekW |
Maximum Electrical Efficiency |
35.70% |
Maximum Standby Rating |
1300 kW |
RPM |
1800 |
Aspiration |
TA |
Bore |
6.7in |
Displacement |
4210in³ |
Engine Model |
G3516B |
Stroke |
7.5in |
Dry Weight - Genset |
27823lb |
Height |
95in |
Length |
165in |
Width |
85in |
Standard Equipment:
-
- Air Inlet
-
- Single element canister type air cleaner with service indicator
- Modular air cleaner, single element service indicator
-
- Control Panel
-
-
- Cooling
-
- CAT flange connections
- Engine driven water pumps for jacket water and aftercooler
- Jacket water and SCAC thermostats
-
- Circuit Breaker
-
- Left, Right, or Rear-Mounted
- 1600A-2000A, 3-Pole UL Rated Circuit Breakers
-
- Exhaust
-
- Provides exhaust port temperatures and stack temperature to customer supplied screen via CCM
- Dry exhaust manifolds, insulated and shielded
- CAT flanged faced outlets
-
- Fuel System
-
- Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
- 24V DC engerized-to-run gas shutoff valve
- Throttle plate, hydraulically actuated and controlled by GECM
-
- Fuel System
-
- Electronic fuel metering valve
- Gas shutoff valve
- Electric air-fuel ratio control
-
- Ignition System
-
- Individual Cylinder Detonation Sensitive Timing (DST)�
- Electronic Ignition System (controlled by GECM)
-
- Generator
-
- Stator RTDs
- Form would stator
- Permanent magnet excitation
- IEC Platinum stator RTDs
- Caterpillar's digital voltage regulator (CDVR) with droop capability, 3-phase sensing, KVAR/PF modes
- Anti-condensation space heater
- Winding temperature detectors
-
- Govrerning System
-
Optional Equipment:
-
- Air Inlet
-
- Air inlet adapters- rectangular or round
-
- Circuit Breaker
-
- 3 Pole UL 489 Listed
- 3 Pole IEC 947-2 Rated
- 1200A, 1600A, 2000A, 2500A, 3200A circuit breaker with shunt trip and auxiliary contacts
-
- Control Panel
-
- Local alarm module
- PL1000E/PL1000T communications module
- Synchronizing module
- Engine failure relay
- Remote annuciator
- Customer Interface Module
-
- Cooling
-
- Flexible connection for jacket water inlet and outlet
-
- Exhaust
-
- 203mm/305mm Elbow
- Flexible Fitting (203mm)
- Flange
- 15 dBA, 356mm (14 in) muffler attenuation
- Exhaust Expander
-
- Fuel System
-
- Fuel filter/ Gas filter
- 206-412 kPa (30-60psi) gas knockdown regulator
-
- Generator
-
- Generator air filter
- Low voltage extension box
- 2400V delta conversion
- Medium and high voltage generators and attachment
- Manual voltage control
- Bearing temperature detectors
- 3-phase, 380/480/600/4160V @ 1800rpm generator (60 Hz)
- European bus bar
- Cable access box
-
- General
-
- Digital diagnostic tool
- US AID Emblem
- Tool set
- Special paint order
-
- Starting/charging
-
- Charging alternator
- 10A/20A Battery charger
- Jacket water coolant heater
- Electric starting motor LH
- 24V Battery Set